Sub-synchronous control interaction (SSCI) is an oscillatory interaction between converter controls and the electrical network at frequencies below the fundamental, and it depends on so many factors — wind speed, filter settings, control mode, grid strength — that testing every case in full time-domain is impractical. The impedance scan offers a way out: characterise each side as a frequency-dependent impedance, combine them, and read off where the combination looks unstable. It is a fast screen for the risky operating modes before any heavy EMT validation. This is a different question from the harmonic frequency scan: harmonic studies look at the distortion produced by injected harmonic currents, whereas SSCI impedance scanning looks at the stability of the interaction between converter control and the network impedance.
Time-Domain Impedance Scanning for SSCI
Time-domain impedance scanning that combines the grid and turbine impedance for SSCI screening.