Reactive power and voltage at the point of interconnection (POI) are a plant-level responsibility, not something each turbine or inverter settles for itself. Above the fast local converter controls sits a supervisory plant controller — the wind-park controller (WPC) on a wind park, the PV plant controller (PPC) on a PV park, identical in logic. It is a slower supervisory layer that watches the active and reactive power at the POI and trims the references handed to the local units so the whole plant meets the operator’s target. Its one central idea, which this guide develops, is that three operating modes — reactive power (Q), voltage (V) and power factor (PF) — all reduce to one common plant-level reactive-power loop.
Plant-Controller Reactive Power Control
Plant-level Q, V and power-factor modes and the secondary voltage control that coordinates the park.