During a grid fault the grid-side converter (GSC) has a finite current capability, and that single limit governs everything that follows. Two distinct but related mechanisms decide how the current is used. Fault-ride-through (FRT) current priority — FRT being the control behaviour that keeps the converter connected and supports the grid through specified voltage disturbances — decides whether active or reactive current wins when the converter is current-limited. Decoupled sequence control (DSC) handles the second-harmonic oscillations that an unbalanced fault stirs up. The cleanest way to hold them apart: FRT decides which current gets priority; DSC decides how the sequence components are controlled. Both run into the same hard limit — the converter’s finite current.
GSC Fault Behaviour: FRT and Decoupled Sequence Control
Why fault-ride-through needs current priority, and why unbalance calls for decoupled sequence control.