United Kingdom
View the UK registered office details.
UK Registered Office
Gretna, Dumfriesshire
Scotland
DG16 5DP
APS provides specialist field testing, commissioning support and condition assessment for MV and HV switchgear assemblies, circuit breakers and Gas-Insulated Switchgear (GIS), verifying dielectric integrity, contact condition, mechanical performance, interlocking logic, protection interface and insulating-gas quality as a complete operational assembly.
MV and HV switchgear, circuit breaker and Gas-Insulated Switchgear commissioning, diagnostic and acceptance testing — verifying the primary current path, operating mechanism, insulation system, gas compartment, interlocks and protection interfaces as a complete operational assembly.
Switchgear and GIS are critical safety and reliability assets within substations, industrial networks, renewable energy plants, data centres, battery energy storage systems and utility distribution and transmission networks. A failure within these assets can result in prolonged outages, equipment damage, safety hazards, loss of supply, delayed energisation or non-compliance with network operator requirements.
APS supports clients through structured testing and diagnostic assessment before energisation, after installation, during periodic maintenance, following faults and as part of asset condition review programmes. The testing approach is aligned with the IEC 62271 series, together with IEC 60270 for partial discharge measurement, IEC 60376 and IEC 60480 for SF6 gas specification and handling, manufacturer instructions, project specifications and DNO/TSO acceptance criteria.
Switchgear defects are commonly associated with insulation degradation, poor contact condition, loose connections, contamination, incorrect assembly, mechanical wear, degraded operating mechanisms, gas-quality deterioration or incorrect protection and control configuration. Many of these are not visible during standard inspection but can be identified through diagnostic testing before the equipment is placed into service.
For GIS in particular, partial discharge measurement, gas quality testing and functional verification are essential because the active parts are sealed and cannot be inspected directly once assembled. APS interprets all results against applicable acceptance limits, manufacturer guidance, baseline measurements and trend data, providing a clear technical position on whether the equipment is suitable for energisation, continued service, further investigation or corrective action.
APS provides structured testing and diagnostic assessment covering the complete switchgear assembly — the primary current path, operating mechanism, insulation system, gas compartment, auxiliary circuits and protection interfaces are verified together rather than as isolated components.
All testing is carried out in accordance with applicable international standards, manufacturer instructions and network operator acceptance criteria.
These services are suitable across the full lifecycle of switchgear and GIS assets, from pre-energisation acceptance through periodic condition monitoring to post-fault diagnostic investigation.
The scope of documentation is agreed with the client at the outset and can be adapted to meet project, network operator or asset-management requirements.
APS tests switchgear, circuit breakers and GIS as an integrated operational system. The primary current path, contacts, operating mechanism, insulation system, gas compartment, interlocks, auxiliary circuits and protection interfaces are verified together, providing far stronger commissioning evidence than isolated component checks.
For circuit breakers, reviewing timing, travel curves, contact synchronism and coil performance identifies sluggish mechanisms, incorrect adjustment, worn linkages, weak coils and pole-discrepancy issues before they cause an in-service failure. For switchgear panels, contact resistance and primary injection confirm correct installation and that the protection system receives the expected signals under operating and fault conditions.
For GIS, partial discharge and gas analysis provide essential evidence of internal condition that inspection cannot reveal once the equipment is sealed. These measurements are the primary technical basis for confirming that internal assembly is correct and that the dielectric system is intact before energisation.
Deliverables may include test schedules, method statements, inspection and test plans (ITPs), commissioning and diagnostic test reports, pass/fail assessment, non-conformance identification, corrective-action recommendations, baseline condition data and technical evidence for energisation approval.