When a circuit breaker opens, the current does not disappear immediately. The process is normally as follows:
- The breaker receives an opening command.
- The contacts start to separate.
- An arc is formed between the contacts.
- The AC current reaches a natural current zero.
- The arc is extinguished.
- A voltage appears across the open breaker contacts.
- The breaker contact gap must withstand this voltage.
The most important point is this: after the arc is extinguished, the breaker must recover its dielectric strength quickly enough to withstand the voltage appearing across its open contacts.
If the voltage across the contacts becomes higher than the dielectric withstand of the gap, the arc can return. This return of the arc is called either:
- Re-ignition, if it happens very soon after interruption.
- Re-strike, if it happens after a longer delay.