Short-line faults and long-line faults are overhead-line fault duties where the transient recovery voltage (TRV) is strongly influenced by travelling waves between the circuit-breaker and the fault location. The interrupted current may be lower than the terminal-fault current, but the TRV can be more severe, because the line-side voltage can rise very quickly after current zero. Circuit-breaker suitability must therefore be checked against the TRV, the RRRV and type-test evidence — not only against short-circuit current magnitude. The severity is also shaped by the fault location, the line surge impedance, travelling-wave reflections, the pole-to-clear sequence, the local capacitances around the circuit-breaker, and the interruption technology.
Short-Line and Long-Line Faults
Travelling-wave TRV duties on overhead lines — the triangular line-side TRV, its rate of rise, surge impedance, the L90 / L75 and T10 duties, ITRV and thermal re-ignition.