This article is Part One of a five-part backflashover series. It introduces the physical mechanism and the basic BFR equation before later parts develop the impulse footing resistance, the CIGRE method, a sensitivity analysis and the line-design implications.
Overhead lines carry shield wires (ground wires) to intercept lightning so that most strokes no longer hit the phase conductors directly. Instead they terminate on the tower top, the shield wire, or a point along the span. A large current then flows down the tower into the footing and earth, and outward along the shield wires to adjacent towers.
That current drives the tower and shield wires to a high transient voltage. The phase conductor is not struck, but the tower voltage can rise so far that the insulation between tower and phase conductor breaks down. This flashover — from the tower/ground side toward the phase conductor — is a backflash (backflashover).